X-VOLT ® NORDIC/TSLF, (3x) - 12/20 (24) kV

AXLJ-F TT – PEX-AL-S-LT

Application

X-VOLT® NORDIC/TSLF is used for medium voltage installations or distribution networks both indoors and outdoors.
Ex. for the supply of transformer stations, infrastructure, wind turbines, solar parks, factory plants, data centers along with others. 

Construction

Conductor

Aluminium, cl. 2
Hygroscopic tapes applied in order to achieve longitudinal watertightness
Conductor screen: cross-linked semiconductor screen (triple-extrusion)

Insulation

Cross-linked polyethylene, DIX8
Insulation screen: cross-linked semiconductor screen (triple-extrusion)

Screen

Screen of Cu threads and metal tape

Outer sheath

PE, DMP 17, black

Technical data

Working temperature

-15° C to +90° C 

Rated voltage

12/20 (24) kV (Uo/U (Um))

Bend radius

15 x cable diameter

CPR classification:

Eca

Please request for DoP at dop@scankab.dk

Approvals

EN 50575, IEC 60754-1/2, HD 620-10K
Bending radius 15 x cable diameter
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -15° C
SKU EAN CPR Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
606131050 5704403205356 Eca 3x1x50/16 184 Drum 58,2 2110
606131095 5704403189106 Eca 3x1x95/25 280 Drum 65,1 2860
606131150 5704403189113 Eca 3x1x150/25 368 Drum 71,6 3565
606131240H25 5704403206926 Eca 3x1x240/25 502 Drum 80,3 5020
606131240 5704403189120 Eca 3x1x240/35 502 Drum 81,3 5020
606131300H25 5704403206933 Eca 3x1x300/25 577 Drum 85,9 5680
606131300 5704403189137 Eca 3x1x300/35 577 Drum 86,9 5680
606131400 5704403189144 Eca 3x1x400/35 673 Drum 92,4 6745
606131630 5704403205363 Eca 3x1x630/35 895 Drum 109,0 9685
* The values can have small deviations