X-VOLT ® NORDIC TSLI, single - 12/20 (24) kV

Application

X-VOLT® NORDIC TSLI is used for medium voltage installations or distribution networks both indoors and outdoors.
Ex. for the supply of transformer stations, infrastructure, wind turbines, solar parks, factory plants, data centers along with others. 

Construction

Conductor

Aluminium, cl. 2
Hygroscopic tapes applied in order to achieve longitudinal watertightness
Conductor screen: cross-linked semiconductor screen (triple-extrusion)

Insulation

Cross-linked polyethylene, DIX8
Insulation screen: cross-linked semiconductor screen (triple-extrusion)

Screen

Screen of Cu threads and Cu tape

Outer sheath

PE, DMP 17, black

Technical data

Working temperature

-15° C to +90° C 

Rated voltage

12/20(24) kV (Uo/U (Um))

Bend radius

15 x cable diameter

CPR classification:

Dca-s1a, d2, a1

Please request for DoP at dop@scankab.dk

Approvals

EN 50575, IEC 60754-1/2, HD 620-10K
Bending radius 15 x cable diameter
Can be buried
Can lay in tubes
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -15° C
Outdoor use
Water resistant
SKU EAN CPR Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
606401050 5704403206018 Dca-s1a,d2,a1 1x50/16 222 Drum 31,1 1055
606401095 5704403206001 Dca-s1a,d2,a1 1x95/25 338 Drum 34,1 1330
606401150 5704403206025 Dca-s1a,d2,a1 1x150/25 440 Drum 26,0 1445
606401240 5704403206032 Dca-s1a,d2,a1 1x240/35 593 Drum 38,0 1765
606401300 5704403206049 Dca-s1a,d2,a1 1x300/35 - Drum - -
606401400 5704403206056 Dca-s1a,d2,a1 1x400/35 769 Drum 43,0 2340
606401630 5704403206063 Dca-s1a,d2,a1 1x630/50 1050 Drum 50,3 3305
606401800 5704403206070 Dca-s1a,d2,a1 1x800/50 1205 Drum 56,0 4035
* The values can have small deviations