X-VOLT ® NORDIC TSLI, (3x) - 12/20 (24) kV

Application

X-VOLT® NORDIC TSLI is used for medium voltage installations or distribution networks both indoors and outdoors.
Ex. for the supply of transformer stations, infrastructure, wind turbines, solar parks, factory plants, data centers along with others. 

Construction

Conductor

Aluminium, cl. 2
Hygroscopic tapes applied in order to achieve longitudinal watertightness
Conductor screen: cross-linked semiconductor screen (triple-extrusion)

Insulation

Cross-linked polyethylene, DIX8
Insulation screen: cross-linked semiconductor screen (triple-extrusion)

Screen

Screen of Cu threads and Cu tape

Outer sheath

PE, DMP 17, black

Technical data

Working temperature

-15° C to +90° C 

Rated voltage

12/20(24) kV (Uo/U (Um))

Bend radius

15 x cable diameter

CPR classification:

Dca-s1a, d2, a1

Please request for DoP at dop@scankab.dk

Approvals

EN 50575, IEC 60754-1/2, HD 620-10K
Bending radius 15 x cable diameter
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -15° C
SKU EAN CPR Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
606431050 5704403206087 Dca-s1a,d2,a1 3x1x50/16 184 Drum 66,8 3190
606431095 5704403206094 Dca-s1a,d2,a1 3x1x95/25 280 Drum 73,3 4030
606431150 5704403206100 Dca-s1a,d2,a1 3x1x150/25 368 Drum 77,2 4370
606431240 5704403206117 Dca-s1a,d2,a1 3x1x240/35 502 Drum 81,4 5350
606431300 5704403206124 Dca-s1a,d2,a1 3x1x300/35 - Drum - -
606431400 5704403206131 Dca-s1a,d2,a1 3x1x400/35 - Drum - -
606431630 5704403206148 Dca-s1a,d2,a1 3x1x630/50 895 Drum 108,1 10015
* The values can have small deviations