NA2XS(F)2Y - 6/10 (12) kV

Application

NA2XS(F)2Y is used for installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Construction

Conductor

Alu-threads, class 2
Extruded semi-conducting layer around the conductor

Insulation

XLPE DIX8
Extruded semi-conducting layer around the insulation
Semi-conducting water blocking tape

Screen

Cu threads and Cu counter helix over tape material
Water blocking tape

Outer sheath

Polyethylene DMP2, black

Comments

Laminated sheath
Polymer laminated aluminum tape 0.25 mm
PE-sheath
Cross and longitudinal watertightness

Technical data

Working temperature

-20° C to +90° C

Rated voltage

6/10 kV (12 kV)

Test voltage

21 kV

Bend radius

15 x cable diameter

Approvals

VDE 0276-620, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
Can be immersed into water
Can lay in tubes
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -20° C
Outdoor use
SKU EAN Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
871011463 - 1X50/16 183 Drum 25 850
871011464 - 1X70/16 228 Drum 27 950
871011465 - 1X95/16 278 Drum 28 1100
871011466 - 1X120/16 321 Drum 30 1200
871011467 - 1X150/25 364 Drum 31 1400
871011468 - 1X185/25 418 Drum 33 1550
871011469 - 1X240/25 494 Drum 35 1750
871011470 - 1X300/25 568 Drum 37 2050
871011471 - 1X400/35 660 Drum 40 2450
871012925 - 1X400/50 660 Drum 40 2200
871011472 - 1X500/35 767 Drum 44 2850
871012053 - 1X630/35 890 Drum 49 2969
871013230 - 1X800/35 1022 Drum 52 3400
871013032 - 1X1000/35 1151 Drum 63 4780
* The values can have small deviations