N2XSY single, CU - 12/20 (24) kV

Application

N2XSY is used for installations indoor as well as outdoor, above or directly in the ground, in tubes or water.

Construction

Conductor

Round Cu threads, class 2
Semi conducting layer around the conductor

Insulation

XLPE insulated
Semi conducting layer around the insulation

Filling sheath

Tape of conductive material

Screen

Cu threads over tape material

Outer sheath

PVC, red

Technical data

Working temperature

-5° C to +90° C

Rated voltage

12/20 kV (24 kV)

Test voltage

42 kV

Bend radius

15 x cable diameter

Approvals

IEC 60502, IEC 60332-1-2, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
Flame retardant acc. to IEC 60332-1
For use in wind turbines
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -5° C
SKU EAN Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
871011295 - 1X35/16 200 Drum 28 1100
871011296 5704403037261 1X50/16 239 Drum 29 1250
871011297 - 1X70/16 297 Drum 31 1500
871011298 5704403119912 1X95/16 361 Drum 32 1800
- - 1X95/25 361 Drum 34 1800
871011318 - 1X120/16 416 Drum 34 2050
871011334 - 1X150/16 470 Drum 35 2300
871011335 5704403114313 1X150/25 470 Drum 35 2400
871011336 - 1X185/16 538 Drum 37 2650
871011299 5704403056262 1X185/25 538 Drum 37 2800
871011337 5704403056279 1X240/16 634 Drum 40 3250
871011338 - 1X240/25 634 Drum 40 3400
871012691 - 1X240/50 634 Drum 40 3499
871011339 5704403037896 1X300/25 724 Drum 42 4000
871011341 5704403185313 1X400/35 829 Drum 45 4950
871011340 - 1X500/35 953 Drum 49 6050
871012566 - 1X630/35 1075 Drum 53 7090
871011529 - 1X800/35 1205 Drum 60 9032
871012692 - 1X800/50 1205 Drum 60 9249
* The values can have small deviations