SCANLET PLUS ® EXQ Premium - 300/500 V

Application

SCANLET PLUS® EXQ Premium installation cables are used in fixed installations or as supply cables, which require the use of environmentally friendly halogen free cables. The cables are suited for all use in building installations and data centers. SCANLET PLUS® Premium can be used in dry and humid areas both indoor and outdoor, built into walls, embedded, or buried in the ground. Conductor insulation is not suitable for direct light exposure.

SCANLET PLUS® EXQ Premium is registered in the database for construction products that can be used in the Nordic Ecolabelled (Svanen) construction. 

SCANLET PLUS® EXQ Premium is evaluated at Byggvarubedömningen and SundaHus (Sweden). 

Construction

Conductor

Single-threaded Cu, class 1

Insulation

Halogen free compound

Conductor color

Green/yellow, blue, brown, black, grey
7G: coloured conductors and green/yellow earth conductor

Outer sheath

Halogen free compound, meter marked, light grey RAL 9002

Technical data

Working temperature

Fixed installation: -30° C to +70° C

Rated voltage

300/500 V

Test voltage

2500 V

Bend radius

8 x cable diameter

Technical comments

Comparable products:
FQQ-light, EXQ-light, IFXI-light

Conductor resistance:
1,5 mm2: 12,1 ohm/km
2,5 mm2: 7,41 ohm/km

CPR classification:

B2ca-s1a,d1,a1

Please request for DoP at dop@scankab.dk

Approvals

EN 50575, HD 604.5D, VDE 0250-215, EN 50618, IEC 60332-1, IEC 60332-3, IEC/EN 61034-2, 50265-1, 50265-2, IEC norms low voltage, CE, RoHS
Bending radius 8 x cable diameter
Can be buried
Can lay in tubes
Environmentally friendly
Fire retardant acc. to IEC 60332-3
Flame retardant acc. to IEC 60332-1
For permanent outdoor installation
For use in cable trays
For use in homes
Halogen free
Low smoke emission during fire acc. to 61034
Low voltage cable
Max. working temp. +70° C
Meter marked
Min. working temperature -30° C
Outdoor use
Suitable for bricking
Suited for public places
Suited for wall attachment
UV-resistant
UV-stabilized
Water resistant
Withstands freezing
SKU EAN CPR Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
122225001 5704403004614 B2ca-s1a,d1,a1 1G2,5 24,0 R-100 5,5 55
122225001T 5704403117116 B2ca-s1a,d1,a1 1G2,5 24,0 T-1000 5,5 55
122615003 5704403047352 B2ca-s1a,d1,a1 3G1,5 17,0 R-100 7,9 110
122615003T 5704403064182 B2ca-s1a,d1,a1 3G1,5 17,0 T-250 7,9 110
122615013 5704403047369 B2ca-s1a,d1,a1 3G1,5 17,0 T-500 7,9 110
122625003 5704403047420 B2ca-s1a,d1,a1 3G2,5 24,0 R-100 8,7 145
122625013T 5704403047536 B2ca-s1a,d1,a1 3G2,5 24,0 T-250 8,7 145
122615005 5704403047376 B2ca-s1a,d1,a1 5G1,5 17,0 R-100 9,2 155
122615005T 5704403064151 B2ca-s1a,d1,a1 5G1,5 17,0 T-250 9,2 155
122615015 5704403047383 B2ca-s1a,d1,a1 5G1,5 17,0 T-500 9,2 155
122625005 5704403047444 B2ca-s1a,d1,a1 5G2,5 24,0 R-100 10,2 210
122625015T 5704403064168 B2ca-s1a,d1,a1 5G2,5 24,0 T-250 10,2 210
122625015 5704403047451 B2ca-s1a,d1,a1 5G2,5 24,0 T-500 10,2 210
122615007 5704403117123 B2ca-s1a,d1,a1 7G1,5 17,0 R-100 9,9 189
122615017 5704403117147 B2ca-s1a,d1,a1 7G1,5 17,0 T-500 9,9 189
* The values can have small deviations