SCANFIRE ® 6040 - 300/500 V

ABA cable

Application

SCANFIRE® 6040 flexible cables are twisted, function secured and used as in FSS facilities as fire warning cables. The cables are halogen free and do not develop corrosive gasses in case of fire. The cables are used in hospitals, airports, public buildings, data centers and malls. Outdoor in pipes or covered in cable trays.

Construction

Conductor

Stranded core, class 5

Insulation

Special silicone rubber

Conductor color

Blue, brown
Fire Barrier (≥ 2 pairs) : Fiberglass tape

Outer sheath

Halogen free fire retardant compound, white

Technical data

Working temperature

-30° C to +90° C

Rated voltage

300/500 V

Bend radius

8 x cable diameter

Technical comments

Conductor resistance: 19.5 Ohm/km
Insulation resistance:  >300 Ohm/km

Firetested at 850 °C acc. to EN 50200

CPR classification:

Dca-s2,d2,a1

Please request for DoP at dop@scankab.dk

Approvals

EN 50575, EN 50200 / IEC 60331-2, EN 50290-2, IEC 60331, IEC 60332-1, IEC 60332-3, IEC 60754, IEC 61034, EN 50200 PH90, CE, RoHS
Bending radius 8 x cable diameter
Environmentally friendly
Fire retardant acc. to IEC 60332-3
Flame retardant acc. to IEC 60332-1
For emergency circuits
For use in homes
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Low smoke emission during fire acc. to 61034
Max. working temp. +90° C
Min. working temperature -30° C
Operation secured acc. to IEC 60331
Suited for public places
UV-resistant
SKU EAN CPR Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
699000309 5704403039302 - 1x2x1 15 T-500 5,9 57
699000309D 5704403202638 Dca-s2,d2,a1 1x2x1 15 T-500 5,9 57
699000215 5704403039173 - 1x2x1,5 16,5 T-500 7,2 82
699000215D 5704403202645 Dca-s2,d2,a1 1x2x1,5 16,5 T-500 7,2 82
699000225 5704403040605 - 1x2x2,5 21 T-500 8,2 114
699000225D 5704403202652 Dca-s2,d2,a1 1x2x2,5 21 T-500 8,2 114
699002210 5704403198382 - 2x2x1 15 T-500 9,2 105
699005210 5704403198399 - 5x2x1 15 T-500 11,8 210
699010210 5704403198375 - 10x2x1 15 T-500 16,6 370
* The values can have small deviations