SCANFIRE® EMC 6015 is EMC screened and suitable for fixed installation, where there is requirements for power supply during a fire for up to 3 hours (750° C) to motors and ventilators, which are frequency controlled and needs to keep functionality during a fire. F.ex. exhaust fan in an apartment building and exhaust in parking garages.
Stranded bare copper wires
Cores are stranded
Fire resistant silicon rubber
Brown, black, grey, yellow/green
100% covering screen consisting of:
aluminum / polyester separator and tinned braided Cu screen
HFFR, black RAL 9005, UV resistant
Fixed installation: -30° C to +90° C
Flexible installation: -5° C to +60° C
0.6/1 kV
4000 V
Conductor resistance (max.): 13.3 Ohm / km
Insulation resistance (min.): 200 MOhm x km
B2ca-s2,d2,a1
Please request for DoP at dop@scankab.dkSKU | EAN | CPR | Dimension (mm2) | Current Value (A) | Packaging | Diameter (mm)* | Weight (kg/km)* |
---|---|---|---|---|---|---|---|
699000415 | 5704403083381 | - | 4G1,5 | 24 | D./Cut | 10,1 | 158 |
699000415B | 5704403202591 | B2ca-s2,d2,a1 | 4G1,5 | 24 | D./Cut | 10,1 | 158 |
699000425 | 5704403104796 | - | 4G2,5 | 32 | D./Cut | 10,8 | 195 |
699000425B | 5704403202607 | B2ca-s2,d2,a1 | 4G2,5 | 32 | D./Cut | 10,8 | 195 |
699000460 | 5704403123766 | - | 4G6 | 54 | D./Cut | 16,0 | 430 |
699000460B | 5704403202614 | B2ca-s2,d2,a1 | 4G6 | 54 | D./Cut | 16,0 | 430 |
699000410B | 5704403202706 | B2ca-s2,d2,a1 | 4G10 | 72 | D./Cut | 17,9 | 681 |
699000416 | 5704403125432 | - | 4G16 | 100 | D./Cut | 20,6 | 970 |
699000416B | 5704403202621 | B2ca-s2,d2,a1 | 4G16 | 100 | D./Cut | 20,6 | 970 |
* The values can have small deviations |