X-VOLT® RHZ1-OL(S), AL with fire-retardant sheath is used for medium voltage installations or distribution networks both indoors and outdoors. For example, for supplying transformer stations, infrastructure, wind turbines, solar parks, factory facilities, data centers, and similar applications.
Aluminium, cl. 2
Cross-linked polyethylene type XLPE according to IEC 60502-2 and type DIX3 according to HD 620-1, natural color.
Semiconducting layer around the isolation. Easy strippable.
Screen of Cu threads and hygroscopic tape
Halogen free polyolefine type DMZ1 acc. to 620-1 and type ST7 acc. to IEC 60502-2, red with two grey stripes.
-15° C to +90° C
12/20 (24) kV
15 x cable diameter
Short circuit temp.: max 250° C / 5 sec.
Eca
Please request for DoP at dop@scankab.dkSKU | EAN | CPR | Dimension (mm2) | Current Value (A) | Packaging | Diameter (mm)* | Weight (kg/km)* |
---|---|---|---|---|---|---|---|
10301095.H25WSI | 5704403211029 | Eca | 1x95/25 | 280 | Drum | 28,6 | 1015 |
10301150.H25WSI | 5704403211036 | Eca | 1x150/25 | 368 | Drum | 31,6 | 1250 |
10301240.H35WSI | 5704403211043 | Eca | 1x240/35 | 502 | Drum | 36,1 | 1705 |
10301400.H35WSI | 5704403211807 | Eca | 1x400/35 | 673 | Drum | 41,9 | 2325 |
10301630.H50WSI | 5704403212439 | Eca | 1x630/50 | 895 | Drum | 50,0 | 3355 |
* The values can have small deviations |