X-VOLT NORDIC, single - 18/30 (36) kV

AXLJ-F TT – TSLF – PEX-AL-S-LT

Application

X-VOLT NORDIC is used for medium voltage installations or distribution networks both indoors and outdoors.
Ex. for the supply of transformer stations, infrastructure, wind turbines, solar parks, factory plants, data centers along with others. 

Construction

Conductor

Aluminium, cl. 2
Hygroscopic tapes applied in order to achieve longitudinal watertightness
Conductor screen: cross-linked semiconductor screen (triple-extrusion)

Insulation

Cross-linked polyethylene, DIX8
Insulation screen: cross-linked semiconductor screen (triple-extrusion)

Screen

Screen of Cu threads and Cu tape

Outer sheath

PE, DMP 17, black

Technical data

Working temperature

-15° C to +90° C 

Rated voltage

36 kV

Test voltage

18/30 kV

Bend radius

15 x cable diameter

Approvals

Bending radius 15 x cable diameter
Halogen free
Max. short circuit temp. +250° C
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -15° C
SKU EAN Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
606201095 5704403189151 1x95/25 338 Drum - -
606201150 5704403189168 1x150/35 440 Drum 38,9 1640
606201240 5704403189175 1x240/35 593 Drum 43,2 2055
606201300 5704403189182 1x300/35 - Drum - -
606201400 5704403189199 1x400/35 769 Drum 49,8 2735
606201630 5704403189205 1x630/50 1059 Drum 57,3 3785
* The values can have small deviations