SCAN ® FLEX - 300/500 V

Application

SCANFLEX® XCH is used in dry and moist rooms for light and medium mechanical stresses. As supply or interconnecting cable for measuring, controlling and regulating, acc. to DIN VDE 0113 for computer units for control equipments on machine tools, assembly lines. For control equipment on conveyors and production lines for controlling, regulating, and monitoring work processes, industrial plants and production. Can be used outdoor.

Construction

Conductor

Stranded electrolytic annealed Cu (IEC/EN 228/VDE 0295/HD 383/BS 6360), class 5

Insulation

HFFR (EN 50290-2/HD 624.6S1/VDE 0207-HI2)

Screen

AL-PES tape
Tinned Cu wire braiding (60% coverage)

Outer sheath

HFFR (EN 50290-1/HD 624.7 S1/VDE 0207-HM2), black, UV resistant

Technical data

Working temperature
Flexible: -5º C to +90º C
Fixed: -30º C to +90º C
Rated voltage

300/500 V

Test voltage

2500 V

Bend radius
Flexible: 15 x cable diameter
Fixed: 7,5 x cable diameter
Technical comments

Insulation resistance: min. 200 MΩ x km.
Inductance: ca. 0,65 mH/km.

Approvals

VDE 0812, IEC/EN 60332-1, VDE 0482-265-2-1, IEC/EN 61034-2/(HD 606)/BS 7622, IEC 60754-2 / EN 50267 (HD 602), IEC 60332-3 CAT A, HAR, CE, RoHS
Bending radius 15 x cable diameter
Electromagnetically protected
Fire retardant acc. to IEC 60332-3
Flame retardant acc. to IEC 60332-1
Halogen free
Impact resistance: medium
Low emission of corrosive gases acc. to IEC 60754
Low smoke emission during fire acc. to 61034
Low voltage cable
Max. working temp. +90° C
SKU EAN Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
- - 3x2,5 - D./Cut 8,1 140