X-VOLT RHZ1-OL, AL - 12/20 kV

Application

X-VOLT RHZ1-OL is used for transportation of medium voltage power. Can be used for industrial installations or for a distribution network. Designed for fixed installations indoors, outdoors or in burried installations.

Construction

Conductor

Electrolytic compressed aluminium, class 2 acc. to EN 60228/IEC 60228
Semiconducting layer around the conductor

Insulation

XLPE. Semiconducting layer around the isolation. Easy strippable

Screen

Screen of Cu threads and hygroscopic tape

Outer sheath

Halogen free polyolefine type DMZ1 acc. to 620-1 and type ST7 acc. to IEC 60502-2, red

Comments

Hygroscopic tape wich completely covers the screen

Technical data

Working temperature

-15° C to +90° C

Rated voltage

12/20 (24) kV

Bend radius

15 x cable diameter

Technical comments

Short circuit temp.: max 250° C / 5 sec.

Approvals

EN 50267 / IEC 60754, EN 60228 / IEC 60228, IEC 60502-2, UNE-HD 620-10E, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
For industrial use
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
SKU EAN Dimension (mm2) Current Value (A) Packaging Diameter (mm)* Weight (kg/km)*
10301095.W 5704403063642 1x95/16 255 D./Cut 31,2 980
10301150.W 5704403063659 1x150/16 335 D./Cut 34,8 1235
10301185.W - 1x185/16 385 D./Cut 36,6 1380
10301240.W 5704403063147 1x240/16 455 D./Cut 39,1 1610
10301240H25W 5704403063727 1x240/25 455 D./Cut 39,6 1740
10301240.W 5704403063147 1x240/16 455 D./Cut 39,1 1610
- - 1x300/16 520 D./Cut 40,9 1820
10301400.W 5704403054923 1x400/16 610 D./Cut 45,0 2175
10301500.W - 1x500/16 720 D./Cut 48,6 2530
10301630.W 5704403090662 1x630/16 840 D./Cut 53,1 3070
10301630.H50W 5704403075737 1x630/50 840 D./Cut - -
* The values can have small deviations